For 120 vac connect the black wire to hot white wire to neutral and cap off the orange wire. Lighting lighting controls occupancy sensors accessories power pack products related to pp20 power pack or visit the sensor switch site.
Sensor Switch Catalog By Alcon Lighting Issuu
Pp20 wiring diagram. 2 pole 120277 vac voltage 120277 vac. 745975809592 nlight power pack sespp20 sensor switch pp20 accessories occupancy sensors lighting lighting controls. 60 hz switching load 120277 vac 2 pole independent switching see table for contact rating use 14 awg wire inputs diode pulse 18awg wire. 2 pole 120277vac designed for use with diversa load occupancy sensors and diode pulse relays. Power packs are the heart of the low voltage sensor system. Wiring diagrams blk 120 v pp20 orn 277 v blk 120 v pp20 orn 277 v.
For help with power pack from sensor switch. For 240 277 vac connect the orange to hot white to neutral and cap off the black wire. Wiring multiple power packs together one sensor controlling two circuits standard wiring the power pack must be connected to a single phase hot and neutral system. The power pack must be connected to a single phase hot and neutral system. For 120 vac connect the black wire to hot white wire to neutral and cap off the orange wire. Wiring multiple power packs together typical wiring diagrams do not wire hot note.
The pp20 transforms 120 240 or 277 volts to class ii 15 vdc to power the remote sensors. Utilizing our patented relay circuit protection the pp20 also switches the lighting load on and off. Pp20 power pack with 20 amp relay by sensor switch. For 220 277 vac connect the orange to hot white to neutral and cap off the black wire. Click add to cart to buy sensor switch pp20 power packalso known as.